VX-2000DS Emergency Power Supply (ER/UK Version)

VX-2000DS Emergency Power Supply (ER/UK Version)

VX-2000DS Emergency Power Supply (ER/UK Version)

VX-2000DS ER/UK

The VX-2000DS Emergency Power Supply Unit supplies the DC power to each equipment in the SX-2000 system by connecting the VX-200PS Power Supply Unit. It keeps the battery unit that contains 2 × 12 V sealed lead batteries charged compensating for the temperature of the battery charging voltage. When the DC power supply from the VX-200PS stops, the VX-2000DS is automatically switched to the backup battery.

EN certification

Power Source230 V AC, 50/60 Hz
Power Consumption240 W max.
Applicable BatteryPanasonic LC-X1265PG/APG (65 Ah)
Charging MethodTrickle charging
Charging Current5 A max.
Charging Output Voltage27.3 V ±0.3 V (at 25 ℃ (77 ゜F))
Temperature correction coefficient: -40 mV/℃
Power Supply Input6 M4 screw terminal, distance between barriers: 11 mm (0.43")
DC Power Output6 (25 A max. each) M4 screw terminal, distance between barriers: 11 mm (0.43")
Control ConnectorRJ45 female connector for connecting the VX-2000SF Surveillance Frame.
Twisted-pair straight cable (TIA/EIA-568A standard)
Type of control signal: Battery check, AC power status, DC power status,
charging circuit failure, and battery failure
Battery Connection1 pair of positive and negative terminals
Applicable cable diameter: AWG 6 - AWG 0 (1/0) (Line resistance within
4 mΩ/total)
2
Cross sectional area: 16 - 50 mm
Operating Temperature0 ℃ to +40 ℃ (32 ゜F to 104 ゜F)
FinishPanel: Surface-treated steel plate, black, 30 % gloss, paint
Dimensions482 (W) × 88.4 (H) × 377.6 (D) mm (18.98" × 3.48" × 14.87")
Weight10.5 kg (23.15 lb)
AccessoryRack mounting screw …4, Fiber washer …4, Blade fuse (40 A) …3,
Fuse (T3.15A L) …1, Power cord (2 m (6.56 ft)) …1, Insulating sheet …1,
Attention label (German) …1, Fastener hook …4, Fastener loop …4
Sticker (Declaration of compliance) …1, Thermal insulating sheet …1
Fuse RatingBlade fuse (40 A), Blade fuse (7.5 A), Fuse (T3.15A)
Internal ResistanceMaximum internal resistance of the battery and its associated circuitry,
Ri max: 50 mΩ
Current SpecificationMaximum output current draw from the battery: 43.5 A
Rated maximum continuous output current, I max a: 43.5 A
Rated maximum short duration output current, I max b: 43.5 A
Rated minimum output current, I min: 0 A
Cable SpecificationRecommended cable parameter for DS-SF Link:
Twisted-pair straight cable (TIA/EIA-568A standard)