VX-015DA
The VX-015DA is an Digital power amplifier used for the VX-3000 systems which is compliant with the European Standard EN54 for fire alarm systems.It is a module type with 1 channel of class-D digital power amplifier, which contribute to energy-saving and light weight design. The VX-015DA also features standby mode to be set for reducing standby power consumption. It requires a dedicated control units VX-3004F, VX-3008F, VX-3016F and power supply units VX-3000DS, VX-3150DS.
Power Source | 31 V DC (operating range: 20 - 33 V DC) DC power in: M4 screw terminal, distance between barriers: 11 mm (0.43") |
---|---|
Amplification System | Class D |
Power Consumption | 1.3 W (standby mode), 14 W (no audio input) 40 W (1/8 rated output), 190 W (rated output) at 31 V DC, output voltage selection switch: 100 V |
Rated Output Power | 150 W (at 100 V line and min. impedance and max. capacitive load) 105 W (at 70 V line and min. impedance and max. capacitive load) 75 W (at 50 V line and min. impedance and max. capacitive load) (at AC Mains VX-3000DS or VX-3150DS: 187 - 253 V) |
Output Voltage | 100 V (70 V, 50 V: selectable) |
Minimum Impedance Load | 67 Ω (at 100 V line), 47 Ω (at 70 V line), 33 Ω (at 50 V line) |
Maximum Capacitive Load | 0.5 μF |
Number of Channels | 1 |
Input | DA CONTROL LINK: Nylon connector (15 pins) |
Output | DA OUTPUT LINK: Nylon connector (2 pins) |
Frequency Response | 40 Hz - 20 kHz: -5 to +1 dB (at 100 V line, 30 dB (*1) output) |
Distortion | 1 % or less (at 100 V line, rated output, 1 kHz) |
Signal to Noise Ratio | 100 dB or more (at 100 V line, A-weighted) |
Operating Temperature | -5 ℃ to +45 ℃ (23 ゜F to 113 ゜F) |
Operating Humidity | 90 %RH or less (no condensation) |
Finish | Surface-treated steel plate |
Dimensions | 82.8 (W) × 91 (H) × 358.2 (D) mm (3.26" × 3.58" × 14.1") |
Weight | 1.3 kg (2.87 lb) |
Accessory | DA CONTROL LINK Cable …1, DA OUTPUT LINK Cable …1, DC FUSE (10 A) …1 |